GEM Setup Overview
Page 5
GEM SETUP OVERVIEW
WEB INTERFACE PERFORMANCE
The performance of the setup interface is greatly improved by setting the GEM to “115200” baud.
The “baud rate” is the speed at which the GEM communicates with the browser. Early versions of the
GEM used “19,200” baud exclusively however newer versions of the firmware provides a means of
increasing the communication speed to “115,200”. The baud rate may be changed using the setup
interface or using the GEM Network Utility program.
Initial Entry
Opening the web interface may require clicking the browser’s address bar a couple of times with a long
pause in between. Once “Setup Mode” is entered, the performance will improve since the GEM will then
focus its resources on the interface.
Slow Page Load
The web interface is a bit slow at loading pages therefore wait until a page is fully loaded before clicking
another menu. If a page fails to load properly, simply wait a couple of seconds and refresh the browser.
Auto Refresh Pages
The “Watt” and “Watt-Hour” pages are automatically refreshed every eight seconds. When switching to
another menu from either one of these two menus, the page may not respond properly. Simply wait and
refresh the browser’s page and a proper display will eventually result.
Be Patient
Try to avoid clicking any page buttons several times. Sometimes there will be a couple of seconds delay
before the page loads.
Exit Setup Mode When Done
It is important to properly exit “Setup Mode” when done to allow the GEM to return to normal
operation.
BEHAVIOR
When entering “Setup Mode”, the GEM stops sending packets or “keep-alive” characters
Packet send will resume when “Setup Mode” is exited
If web setup pages are inactive for 15 minutes, the GEM will automatically exit “Setup Mode
and resume sending packets
If “Watt” or “Watt-Hour” menu is selected and “Setup Mode” is not properly exited, the GEM
will not automatically exit this mode due to the auto-refresh nature of these two menu options.
Closing the browser will allow the GEM to exit “Setup Mode” after 15 minutes.
QUICK START
Quick start instructions are provided in the “Quick Start” chapter on page 39.